
Growbud Controller
Price
Overview
Control
Communication
Sensing
Power
Power supplyincluded, plugs straight into the controller
Assembled in the USA
Built to order, not held on a shelf
Every Growbud sensor and controller is assembled in the United States. We are scaling production, so most orders ship in about 6-8 weeks rather than the same day. Placing an order reserves your units from the next build.
- Pay now and we email tracking the day it ships, or reserve your units without paying and settle when it leaves. Your choice.
- Stocked inventory with immediate shipping is coming as capacity grows.
- The 90-day return window starts when your order arrives, not when you place it.
- Free US shipping over $500.
Thank you for your patience while we build up. If you have a deadline or a install date to hit, tell us about it and we will give you a straight answer on timing.
Product Details
Works with Growbud App Platform
Free Professional-Grade Monitoring and Analytics
Real-Time Monitoring
- Live sensor data streaming with sub-second updates
- Customizable alerts and notifications
- Historical data tracking and trend analysis
Advanced Analytics
- AI-powered insights and recommendations
- Multi-sensor comparison and correlation
- Export data for research and reporting
Download the free Growbud app to unlock the full potential of your Growbud Controller
Technical Specifications
Valve Zones
4 Channels
24 VAC or latching DC solenoids. Each AC channel carries 1.35 A RMS, about 0.95 A derated at 50 °C, and all four share a resettable fuse passing about 2.2 A, so several coils can share one output but four typical 0.6 A solenoids held at once is over the limit: stagger the zones or choose lower-current coils. Latching DC fires one channel at a time, peaking at 3 A. Valve type is set in configuration. In DC mode contact A (brown) is positive and B (blue) is negative: red to brown, black to blue
Sensor Inputs
4 Universal
Every valve port is also a sensor port: pulse, dry contact, or hall-effect flow, 4-20 mA, 0-10 V, or 0-3.3 V, each selected in firmware with switched 12 V excitation. Specify flow meters at or below roughly 500 pulses/litre
Leak Probes
2 Ports
Two identical two-electrode probe ports; either port takes either probe
RS-485 / CAN
Modbus + CANopen
One port, two buses: Modbus master for up to 128 wired sensors, Modbus slave or BACnet MS/TP for your BMS, or CANopen master/slave for actuators and industrial control. Switched, fused, current-monitored 12 V 0.75 A sensor power on the same cordset
BACnet
MS/TP + IP
Native building automation objects with priority arrays
Wireless
LoRaWAN + BLE
Miles of range on LoRaWAN; Bluetooth for phone setup
Circuit Protection
Auto-Reset Fuses
Self-resetting PTCs on every valve channel and on the supply input. An overload clears itself once the fault is removed, with no fuses to replace in the field
Power Input
USB-C PD / 12 VDC / 24 VAC
USB-C PD 5-20 V up to 20 W, 9-30 VDC nominal 12 V, or 20-26 VAC RMS nominal 24 V. The powered rail is detected at boot, fused and surge-protected
Scheduling
16 On-Board
Schedules run autonomously without a network connection
Deployment Scenarios
The Growbud Controller fits into your operation two ways: fully wireless alongside your Growbud sensors, or hardwired into your building management system. The RS-485 / CAN port does one job at a time: Modbus master to your industrial sensors, CAN master or slave to actuators and industrial control, or the building-system connection over Modbus slave or BACnet, with nearby Growbud sensors picked up over Bluetooth. Every configuration drives up to four valve zones, 24 VAC or latching DC, with one drive mode per unit, never mixed, and each of those four ports also reads a sensor. The valve counts below are just sample setups.

Wireless: LoRaWAN
Deploy the Controller exactly like your Dro and Vero sensors. Controller and sensors all join the same Growbud gateway. Shown here driving four 24 VAC valve zones on the irrigation manifold.
- • Controller + Dro/Vero sensors on one LoRaWAN network
- • Sample config: 4 AC valve zones on one 24 VAC supply
- • Wire RS-485 Modbus sensors (EC, pH, flow) straight in
- • Miles of range; on-board schedules if the network drops

Building Automation: BACnet
Wire the field-bus port into your BMS as a BACnet MS/TP node. Two leak probes watch the floor, a dry-contact power relay stands ready to shut the pump down, and air-quality monitors report in alongside, all surfaced to the building system as BACnet objects.
- • BACnet MS/TP on RS-485 (BACnet/IP via gateway)
- • Two identical leak-probe ports; either takes either probe
- • Valve output drives a dry-contact relay for pump shutoff
- • Air quality, leak, and power control in one node
Valve drive
One controller, either kind of valve
24 VAC triac drive
20-26 VAC RMS · 1.35 A per channel
Polarity does not apply: the output is energised or it is not. Every channel is individually protected with self-resetting fuses, so doubling two or three small solenoids onto one output is fine. High-current zones simply run in sequence from the schedule.
Drive mode applies to all four outputs, so every valve on a controller is the same type — never mix 24 VAC and DC on one unit.
Connector Pinouts
Every port on the Growbud Controller uses standard M12 and M8 A-coded connectors. Tap a contact on the face view to see its signal, or use standard IEC-colour cordsets and match by conductor colour. Each of the four valve ports drives a valve and reads a sensor, and the two leak ports are interchangeable.
Power from one pair only: DC (1/2) or AC (3/4), never both.
M12 A-coded input · separate DC and floating AC pairs
Power input (J1)
| Pin | Wire | Signal | Function |
|---|---|---|---|
| 1 | Brown | VDC_IN | 9–30 VDC input |
| 2 | White | GND | DC return / circuit ground |
| 3 | Blue | VAC_HOT | 20–26 VAC RMS input; the HVAC R power leg |
| 4 | Black | VAC_RETURN | Floating AC return, the HVAC C common; not DC ground |
| 5 | Grey | NC | Not connected |
- IEC blue normally means 0 V. On the Power connector it does not: contact 3 is 24 VAC hot. Never treat the blue conductor here as a return.
- Coming from HVAC: contact 3 is the equivalent of the red R power wire and contact 4 is C, the common.
- Never bond contact 4 to contact 2 in the cable; the AC input is differential.
- Use either the DC pair (1/2) or the AC pair (3/4), not both supplies at once.
- Contact 5 is not connected. The grey conductor of a standard cordset is unused here.
Conductor colours follow IEC 60947-5-2 for standard A-coded cordsets. Terminate cable shields at one end only, away from the controller: no contact on any port grounds the shield at the controller end. Full wiring detail, register maps, and installation procedures are in the Growbud Controller manual.
Wiring
DC solenoid polarity
On a latching DC solenoid, valve contact A is positive and B is negative. On the M12 cable that is the brown conductor to A and the blue to B, so a typical solenoid wires red to brown, black to blue.
Getting it backwards will not damage the solenoid. It swaps which pulse opens the valve and which closes it, so the zone runs inverted and the Controller reports open while the valve is actually shut. If a zone behaves backwards, swap A and B.
In AC mode none of this applies. The output is simply energised or not, so A and B can go either way round. Only DC latching drive depends on wiring order for open versus closed.
Technical Documentation
Access comprehensive technical specifications, installation instructions, and usage guidelines for your Growbud Controller by downloading the product manual below.
Download Growbud Controller Manual (PDF)For additional support or questions about your product, please contact our technical support team.


